tecned-logo-for-menupage

X – Pnd UPS

Endurance 6-10kVA

X-Pnd 60-1200kVA

Features and Advantages

High Reliability:

• Wide input voltage range +/- 20% (up to -40% at reduced load)
• Hot-swappable function ensures uninterrupted operations during maintenance
• Dual system control card prevents single failure point
• Intelligent fan control and redundant design for energy saving: 25% load can be driven when 2 fans
fail and 50% load when 1 fan fails
• Parallel expansion up to four systems without requiring additional hardware

High Performance:

• High efficiency in online mode (>97%) reduces heat dissipation and limits power consumption costs
• THDi≤3% and input power factor 0.99 reduce the pollution to grid and reduce upstream investment costs
• Full rated power (kVA=kW) to maximize power availability
• Efficiency>99% in ECO mode gives significant cost reduction
• Advanced power module sleep mode, prolong the service life of power module
• Allow 100% three phase unbalance load
• Frequency converter function(60Hz to 50Hz or 50Hz to 60Hz)
• Loop test function without load enables on-site commission
• Small footprint, 300kW only covers 0.5m2

X-Pnd 60-120kVA

MODEL X-PND 60 X-PND 90 X-PND 120
Power module Model XPD - 30
Input
Voltage Range (Vac) 3Φ4W+PE, 380/400/415, L-L: 138~485
      Input Wiring 3Ph+N+PE
Input Frequency (Hz) 40-70
                Bypass Voltage Range (Vac) -15% (-20%/-30% optional) ~+15%(+10% /+20% optional)
      Power Factor ≥0.99
   THDi at full load <3% linear load, <5% nonlinear load
Battery
       Battery (Vdc) ±192 (±180 ~ ±276 settable)
Charging Current (A) N × 10 Maximum (N = the number of power module)
Output
Power Module (kVA) 30
                   Power Module Number 2 3 4
                   System Capacity (kVA) 60 90 120
     Power Factor 1
     Voltage (Vac) 3Φ4W+PE, L-L:380,400,415 ±1%
   Frequency (Hz) 50/60± 0.2% (battery mode)
                  Three Phase Difference True sine wave,              ≤1 degrees
        THDv ≤1% (linear load, full load); ≤4% (nonlinear load, full load)
               Static Bypass Transfer Time 0
                 System Efficiency (MAX) 96%
            Overload Capacity 101-105% continuous, 106-110% load for 60 minutes, 111%-125% load for 10 minutes, 126%-150% load for 1 minute, over 150% load transfer to bypass
Others
Display 7-inch Touch screen+ LED+ Physical buttons
Operating Temperature (ºC) 0~40
Storage Temperature (ºC) -40~70
Relative Humidity 0~95%, no condensation
Communication Function RS232, RS485, Dry contact, MODBUS, SNMP (optional)
Noise (dB) 70
Altitude(m) 0~2000, no derate
Cabling Bottom  
Color Jet black RAL 9005
     Power Module Dimension (W×D×H) (mm) 500×700×130
         Cabinet Dimension (W×D×H) (mm) 600×860×2000
             Weight (kg) Cabinet 182
Power Module 24 kg per module

X-Pnd 100-300kVA

MODEL X-PND 100 X-PND 150 X-PND 200 X-PND 250 X-PND 300
Power module Model X-PND 100
Input
Voltage Range (Vac) 3Φ4W+PE, 380/400/415, L-L: 138~485
      Input Wiring 3Ph+N+PE
Input Frequency (Hz) 40-70
                Bypass Voltage Range (Vac) -15% (-20%/-30% optional) ~+15%(+10% /+20% optional)
      Power Factor ≥0.99
   THDi at full load                                 <3% linear load, <5% nonlinear load
Battery
       Battery (Vdc)                          ±192 (±180 ~ ±276 settable)
Charging Current (A) N × 10 Maximum (N = the number of power module)
Output
Power Module (kVA) 50
                   Power Module Number 2 3 4 5 6
                   System Capacity (kVA) 100 150 200 250 300
     Power Factor 1
     Voltage (Vac) 3Φ4W+PE, L-L:380,400,415 ±1%
   Frequency (Hz) 50/60± 0.2% (battery mode)
                  Three Phase Difference True sine wave,              ≤1 degrees
        THDv ≤1% (linear load, full load); ≤4% (nonlinear load, full load)
               Static Bypass Transfer Time 0
                 System Efficiency (MAX) 96%
            Overload Capacity 101-105% continuous, 106-110% load for 60 minutes, 111%-125% load for 10 minutes, 126%-150% load for 1 minute, over 150% load transfer to bypass
Others
Display 7-inch Touch screen+ LED+ Physical buttons
Operating Temperature (ºC) 0~40
Storage Temperature (ºC) -40~70
Relative Humidity 0~95%, no condensation
Communication Function RS232, RS485, Dry contact, MODBUS, SNMP (optional)
Noise (dB) <70
Altitude(m) 0~2000, no derate
Cabling Bottom
Color Light grey RAL 7035
     Power Module Dimension (W×D×H) (mm) 500×700×130
         Cabinet Dimension (W×D×H) (mm) 600×860×2000
             Weight (kg) Cabinet 182 218 247 257 263
Power Module 33 kg per module

X-Pnd 400-1200kVA

MODEL X-PND 400 X-PND 500 X-PND 600 X-PND 800 X-PND 1000 X-PND 1200
Power module Model XPD-100
Input
Voltage Range (Vac) 3Φ4W+PE, 380/400/415, L-L: 138~485
Input Wiring 3Ph+N+PE
Input Frequency (Hz) 40-70
Bypass Voltage Range (Vac) -20% (10/15/30/40/50/60%) ~ +15% (10/20/25%)
Power Factor ≥0.99
     THDi at full load <3% linear load
Battery
Battery Voltage (Vdc)* ±240 (±180~±300 settable)
Charging Current (A) N×30 Maximum (N = the number of power module)
Output
Power Module (kVA) 100
Power Module Number 4 5 6 8 10 12
System Capacity (kVA) 400 500 600 800 1000 1200
Power Factor 1
Voltage (Vac) 3Φ4W+PE, L-L:380,400,415 ±1%
Frequency (Hz) 50/60± 0.2% (battery mode)
Three Phase Difference True sine wave, ≤2 degrees
THDv ≤1% (linear load, full load); ≤4% (nonlinear load, full load)
Static Bypass Transfer Time 0
System Efficiency (MAX) 97%
  Overload Capacity 101-105% Long run, 106-110% load for 60 minutes, 111%-125% load for 10 minutes, 126%-150% load for 1 minute, over 150% load transfer to bypass
Others
Display 7-inch Touch screen+ LED+ Physical buttons
Operating Temperature (ºC) 0~40
Storage Temperature (ºC) -40~70
Relative Humidity 0~95%, no condensation
Communication Function RS232, RS485, Dry contact, MODBUS, SNMP (optional)
Noise (dB) 70
Altitude(m) 0~2000, no derate
Cabling Bottom/Top Top
Color Light grey RAL 7035
   Power Module Dimension (W×D×H) (mm) 500×750×130(3U)
Cabinet Dimension(W×D×H) (mm) 1200×1000×2000 1400x1000×2000 1800x1000×2000
Weight (kg) Cabinet 400 506 580 650 740
Power Module 55 kg per module