High Reliable
• A super wide input voltage range -60%~+25% for high grid adaptability and prolong battery service life.
• Full DSP control technology, ensuring reliable performance
• Intelligent fan speed control reduces the noise and prolongs fan service life
Green Power
• AC/AC efficiency up to 96%, ECO mode up to 98%, less TCO and more energy saving
• Output power factor up to 1.0, more powerful to connect more critical loads
• 3 level IGBT technology for input PF>0.996, THDi <5% (10-20kVA)/THDi<3% (30~40kVA)
Flexible Design
• 3U height tower and rack compatible design
• Adjustable input and output to 33\31\11 configuration
(10~20kVA) and 33\31 configuration (30~40kVA)
• Common battery bank on parallel mode
• LCD Rotate setting by (10-20KVA), gravity autorotate
by (30-40KVA)
• Adjustable battery numbers and charge current
Ecological Power Networ
Optional
• External UPS input and output distribution box
• Dry contact kits and SNMP
• Input and output isolation transformer
• 19 inch rail kits
MODEL | VRP 10kVA | VRP 20kVA | VRP 30kVA | VRP 40kVA |
Input | ||||
Voltage (Vac) | 138-485 (L-L) | |||
Frequency (Hz) | 40-70 | |||
Power Factor | ≥0.99 | |||
THDi | <5% | |||
Output | ||||
Capacity (VA) | 10 | 20 | 30 | 40 |
AC/AC Efficiency Max. | 96% | |||
Power Factor | 0.9 (1.0 at 40oC) | |||
Voltage (Vac) | 380/400/415±1%(L-L) | |||
THDv | THD <2% (linear load), | THD <1% (linear load), | ||
THD < 4% (nonlinear load) | THD < 3% (nonlinear load) | |||
Transfer Time | 0 | |||
Overload | 115%~130% load for 15 min, | |||
131%~155% load for 1 min, | ||||
>155% load: change to bypass immediately | ||||
ECO Mode | Yes | |||
Battery | ||||
Voltage (Vdc) | ±192 (±144~±240 adjustable)/32 pcs default (28-40 pcs adjustable) | |||
Charging Current (A) | 4 (1-10 settable) | 15 (1-20 settable) | ||
Other | ||||
Communication Interface | RS485+EPO | |||
(RS232+dry contact, SNMP are optional in slot) | ||||
Display | Stroke segment LCD | Dot matrix LCD | ||
Alarm | Low battery, abnormal AC input, UPS failure, etc. | |||
Protection | Low battery, overload, short-circuit and over temperature, etc. | |||
Noise (dB) | < 50 | |||
Working Temperature (°C) | -5~40, no derating | -5~50* | ||
Relative Humidity | 0 ~ 95%, no condensation | |||
Dmension (W×D×H) (mm) | ||||
UPS | 438×500×130 (3U) | 438×680×130 (3U) | ||
Distribution Box | 438×500×130 (3U) | 438×680×130 (3U) | ||
UPS | 438×500×130 (3U) | 438×680×130 (3U) | ||
Weight (kg) | ||||
UPS | 20 | 34 | ||
Distribution Box | 8 | 14 | ||
Batt. Pack | 45 (with16×7AH 12V batteries) ×2 pcs |